VO-YMvKas mb 0,6/1 kV
Appearance: Ground cable (1.5 mm² - 6 mm²)
Usage: A cable to be put in the ground and for above-ground installations where, for instance, high mechanical and electrical protection is required. The PVC outer jacket doesn't burn easily and has fire-retardant properties. The multiple-core version is usually used as an auxiliary power cable as well as in measurement and control (instrument) engineering.
Properties:
- The outer jacket has fire-retardant properties
- Maximum continuous conducter temperature 90 C°
Structure: Conductor: Solid bare electrolytic copper. < 6 mm² : Solid. Insulation: Vulcanized polyethylene (XLPE). Cores: Twisted together and padded to a round hole. Inner jacket: Polyvinylchloride (PVC). Plaiting/protective cover: Plaiting of galvanized steel wires on top of a supple flat consisting of many tin-plated copper wires. Outer jacket: Polyvinylchloride (PVC), doesn't burn easily. Jacket colour: Grey (other colours available on request).
Note:
- Also available in a halogen-free version Z1O-YMz1 Kas mbzh 0.6/1 kV.
Electrical details: Nominal voltage: 600/1000 Volt Tested voltage: 3500 Volt
Core colours: 2 cores: Brown, blue 3 cores: Black, grey, brown 4 cores: Black, blue, brown, grey 5 cores: Black, blue, brown, grey, black Muliple cores: Black, consecutively numbered starting from the centre of the cable
Supplied: 2 - 4 cores, 1,5 - 4 mm² : On rings and reels 5 cores 1,5 and 2,5 mm²: On rings ande reels Other sizes: On reels

|
Number of cores and nominal conductor diameter* (n x mm²( | Nominal outside diameter (mm) | Minimum bending radius (mm) | Permissible current** (A) | Maximum tensile strength (N) | Approximate weight (kg/km) |
2 x 1,5 |
12.6 |
76 |
26 |
480 |
250 |
2 x 2,5 |
13.4 |
80 |
34 |
540 |
290 |
2 x 4 |
14.3 |
86 |
44 |
610 |
360 |
2 x 6 |
15.4 |
92 |
56 |
710 |
450 |
2 x 10 s |
20.9 |
146 |
73 |
1310 |
710 |
3 x 1,5 |
13 |
78 |
22 |
510 |
270 |
3 x 2,5 |
13.9 |
83 |
29 |
580 |
320 |
3 x 4 |
14.9 |
89 |
37 |
670 |
410 |
3 x 6 |
16 |
96 |
46 |
770 |
510 |
3 x 10 s |
21.8 |
153 |
61 |
1430 |
810 |
4 x 1,5 |
13.8 |
83 |
22 |
570 |
300 |
4 x 2,5 |
14.7 |
88 |
29 |
650 |
360 |
4 x 4 |
15.8 |
95 |
37 |
750 |
470 |
4 x 6 |
17.2 |
103 |
46 |
890 |
600 |
4 x 10 s |
22.9 |
160 |
61 |
1573 |
930 |
5 x 1,5 |
14.7 |
88 |
22 |
650 |
340 |
5 x 2,5 |
15.7 |
94 |
29 |
740 |
410 |
5 x 4 |
17 |
102 |
37 |
870 |
540 |
5 x 6 |
18.4 |
110 |
46 |
1020 |
690 |
6 x 1,5 |
15 |
90 |
17 |
680 |
340 |
6 x 2,5 |
16.1 |
97 |
22 |
780 |
420 |
7 x 1,5 |
15 |
90 |
16 |
680 |
350 |
7 x 2,5 |
16.1 |
97 |
21 |
780 |
430 |
8 x 1,5 |
15.9 |
95 |
15 |
760 |
390 |
8 x 2,5 |
17.3 |
104 |
20 |
900 |
500 |
10 x 1,5 |
17.8 |
107 |
14 |
950 |
480 |
10 x 2,5 |
19.3 |
116 |
18 |
1120 |
620 |
12 x 1,5 |
18.2 |
109 |
13 |
990 |
500 |
12 x 2,5 |
19.8 |
119 |
17 |
1180 |
630 |
14 x 1,5 |
18.9 |
113 |
12 |
1070 |
540 |
14 x 2,5 |
20.6 |
144 |
16 |
1270 |
700 |
16 x 1,5 |
19.7 |
118 |
11.5 |
1160 |
590 |
16 x 2,5 |
21.5 |
151 |
15 |
1390 |
770 |
19 x 1,5 |
20.6 |
144 |
10.5 |
1270 |
660 |
19 x 2,5 |
22.4 |
157 |
13.5 |
1510 |
860 |
24 x 1,5 |
23.2 |
162 |
9.5 |
1610 |
790 |
24 x 2,5 |
25.4 |
178 |
12.5 |
1940 |
1050 |
30 x 1,5 |
24.4 |
171 |
8.5 |
1790 |
920 |
30 x 2,5 |
26.9 |
188 |
11.5 |
2170 |
1230 |
37 x 1,5 |
26 |
182 |
8 |
2030 |
1070 |
37 x 2,5 |
28.8 |
202 |
11 |
2490 |
1460 |
*) s = twisted conductor. **) The permissible current applies to 1 cable laid directly undergound (basic installation method D of NEN 1010 fifth edition), at a ground temperature of 20 C° and a heat resistance coefficient of the ground of 2.5 k.m/W.
|
 |
VG-YMvKas mb 0,6/1 kV
Appearance: Ground cable (10 mm² - 240 mm²)
Usage: A cable to be put in the ground and for above-ground installations where, for instance, high mechanical and electrical protection is required. Pre-eminently suitable for use as power supply cable for main and sub-distribution units.
Properties:
- The outer jacket has fire-retardant properties
- Maximum continuous conductor temperature 90 C°
Structure: Conductor: Twisted bare electrolytic copper 3 and 4-core cable > 35 mm²: sector-shaped Other types: round Insulation: Vulcanized polyethylene (XLPE) Cores: Round conductors: padded to fill out to a round whole Sector-shaped conductors: wrapped in plastic tape Inner jacket: Polyvinylchloride (PVC) Armouring/protective cover: Wires and bare copper wires, surrounded by an open counter spiral of galvanized steel tape Outer jacket: Polyvinylchloride (PVC), doesn't burn easily Jacket colour: Grey (other colours available on request)
Note:
- Also available in a halogen-free version Z1G-YMz1KaS mbhz 0.6/1 kV.
Electrical details: Nominal voltage: 600/1000 Volt Tested voltage: 3500 Volt
Core colours: 2 cores: Brown, blue 3 cores: Black, brown, grey 4 cores: Black, blue, brown, grey 5 cores: Black, blue, brown, black, grey
Supplied: All sizes: On reels

|
Number of cores and nominal conductor diameter* (n x mm²) | Nominal outside diameter (mm) | Minimum bending radius (mm) | Permissible current** (A) | Maximum tensile strength (N) | Approximate weight (kg/km) |
2 x 10 |
20.2 |
141 |
73 |
3260 |
840 |
2 x 16 |
22.2 |
155 |
95 |
3940 |
1060 |
2 x 25 |
26 |
182 |
121 |
5410 |
1450 |
2 x 35 |
27 |
189 |
146 |
5830 |
1710 |
2 x 50 |
30 |
210 |
173 |
7200 |
2150 |
2 x 70 |
34 |
238 |
213 |
9250 |
2820 |
3 x 10 |
21 |
147 |
61 |
3530 |
950 |
3 x 16 |
23.2 |
162 |
79 |
4310 |
1210 |
3 x 25 |
27 |
189 |
101 |
5830 |
1680 |
3 x 35 SV |
25 |
175 |
122 |
5000 |
1690 |
3 x 50 SV |
26.9 |
188 |
144 |
5790 |
2130 |
3 x 70 SV |
31.4 |
220 |
178 |
7890 |
2870 |
3 x 95 SV |
35.2 |
246 |
211 |
9910 |
3770 |
3 x 120 SV |
39 |
273 |
240 |
10000 |
4670 |
3 x 150 SV |
42.5 |
298 |
271 |
10000 |
5630 |
3 x 185 SV |
46.6 |
326 |
304 |
10000 |
6860 |
3 x 240 SV |
54 |
378 |
351 |
10000 |
9360 |
3 x 300 SV |
57.8 |
405 |
396 |
10000 |
11380 |
4 x 10 |
22.1 |
155 |
61 |
3910 |
1070 |
4 x 16 |
24.9 |
174 |
79 |
4960 |
1470 |
4 x 25 |
29.5 |
207 |
101 |
6960 |
2030 |
4 x 35 SV |
28.2 |
197 |
122 |
6360 |
2090 |
4 x 50 SV |
30.9 |
216 |
144 |
7640 |
2690 |
4 x 70 SV |
35.6 |
249 |
178 |
10000 |
3680 |
4 x 95 SV |
39.6 |
277 |
211 |
10000 |
4850 |
4 x 120 SV |
43.2 |
302 |
240 |
10000 |
5980 |
4 x 150 SV |
47.6 |
333 |
271 |
10000 |
7240 |
4 x 185 SV |
54.1 |
379 |
304 |
10000 |
9490 |
4 x 240 SV |
60.3 |
422 |
351 |
10000 |
12030 |
5 x 10 |
24.1 |
169 |
61 |
4650 |
1270 |
5 x 16 |
26.9 |
188 |
79 |
5790 |
1680 |
*) SV = sector-shaped. **) The permissible current applies to 1 cable laid directly underground (basic installation method D of NEN 1010 fifth edition), at a ground temperature of 20 C° and a heat resistance coefficient of the ground of 2.5 K.m/W.
|