Ground cable YMvKas

Cable

Ground cable

VO-YMvKas mb 0,6/1 kV

Appearance:
Ground cable (1.5 mm² - 6 mm²)

Usage:
A cable to be put in the ground and for above-ground installations where, for instance, high mechanical and electrical protection is required. The PVC outer jacket doesn't burn easily and has fire-retardant properties. The multiple-core version is usually used as an auxiliary power cable as well as in measurement and control (instrument) engineering.

Properties:

  • The outer jacket has fire-retardant properties
  • Maximum continuous conducter temperature 90 C°

Structure:
Conductor:
Solid bare electrolytic copper. < 6 mm² : Solid.
Insulation:
Vulcanized polyethylene (XLPE).
Cores:
Twisted together and padded to a round hole.
Inner jacket:
Polyvinylchloride (PVC).
Plaiting/protective cover:
Plaiting of galvanized steel wires on top of a supple flat consisting of 
many tin-plated copper wires.
Outer jacket:
Polyvinylchloride (PVC), doesn't burn easily.
Jacket colour:
Grey (other colours available on request). 

Note:

  • Also available in a halogen-free version Z1O-YMz1 Kas mbzh 0.6/1 kV.

Electrical details:
Nominal voltage: 600/1000 Volt
Tested voltage: 3500 Volt

Core colours:
2 cores: Brown, blue
3 cores: Black, grey, brown
4 cores: Black, blue, brown, grey
5 cores: Black, blue, brown, grey, black
Muliple cores: Black, consecutively numbered starting from the centre of the cable

Supplied:
2 - 4 cores, 1,5 - 4 mm² : On rings and reels
5 cores 1,5 and 2,5 mm²: On rings ande reels
Other sizes: On reels

 

print

Number of cores and nominal conductor diameter*
(n x mm²( 
Nominal outside diameter
(mm)
Minimum bending radius
(mm)
Permissible current**
(A)
Maximum tensile strength
(N)
Approximate weight
(kg/km)
2 x 1,5 12.6 76 26 480 250 
2 x 2,5 13.4 80 34 540 290
2 x 4 14.3 86 44 610 360 
2 x 6 15.4 92 56 710 450
2 x 10 s 20.9 146 73 1310 710 
3 x 1,5 13 78 22 510 270
3 x 2,5 13.9 83 29 580 320 
3 x 4 14.9 89 37 670 410
3 x 6 16 96 46 770 510 
3 x 10 s 21.8 153 61 1430 810 
4 x 1,5 13.8 83 22 570 300 
4 x 2,5 14.7 88 29 650 360 
4 x 4 15.8 95 37 750 470
4 x 6 17.2 103 46 890 600 
4 x 10 s 22.9 160 61 1573 930 
5 x 1,5 14.7 88 22 650 340
5 x 2,5 15.7 94 29 740 410 
5 x 4 17 102 37 870 540 
5 x 6 18.4 110 46 1020 690
6 x 1,5 15 90 17 680 340 
6 x 2,5 16.1 97 22 780 420 
7 x 1,5 15 90 16 680 350 
7 x 2,5 16.1 97 21 780 430 
8 x 1,5 15.9 95 15 760 390 
8 x 2,5 17.3 104 20 900 500 
10 x 1,5 17.8 107 14 950 480 
10 x 2,5 19.3 116 18 1120 620 
12 x 1,5 18.2 109 13 990 500 
12 x 2,5 19.8 119 17 1180 630 
14 x 1,5 18.9 113 12 1070 540 
14 x 2,5 20.6 144 16 1270 700 
16 x 1,5 19.7 118 11.5 1160 590 
16 x 2,5 21.5 151 15 1390 770 
19 x 1,5 20.6 144 10.5 1270 660 
19 x 2,5 22.4 157 13.5 1510 860 
24 x 1,5 23.2 162 9.5 1610 790 
24 x 2,5 25.4 178 12.5 1940 1050 
30 x 1,5 24.4 171 8.5 1790 920 
30 x 2,5 26.9 188 11.5 2170 1230 
37 x 1,5 26 182 8 2030 1070
37 x 2,5 28.8 202 11 2490 1460 

*) s = twisted conductor.
**) The permissible current applies to 1 cable laid directly undergound (basic installation method D of NEN 1010 fifth edition), at a ground temperature of 20 C° and a heat resistance coefficient of the ground of 2.5 k.m/W. 

 

VG-YMvKas mb 0,6/1 kV

Appearance:
Ground cable (10 mm² - 240 mm²)

Usage:
A cable to be put in the ground and for above-ground installations where, for instance, high mechanical and electrical protection is required. Pre-eminently suitable for use as power supply cable for main and sub-distribution units.

Properties:

  • The outer jacket has fire-retardant properties
  • Maximum continuous conductor temperature 90 C°

Structure:
Conductor:
Twisted bare electrolytic copper 
3 and 4-core cable > 35 mm²: sector-shaped
Other types: round
Insulation:
Vulcanized polyethylene (XLPE)
Cores:
Round conductors: padded to fill out to a round whole
Sector-shaped conductors: wrapped in plastic tape
Inner jacket:
Polyvinylchloride (PVC)
Armouring/protective cover:
Wires and bare copper wires, surrounded by an open counter   
spiral of galvanized steel tape
Outer jacket:
Polyvinylchloride (PVC), doesn't burn easily
Jacket colour: 
Grey (other colours available on request)

Note:

  • Also available in a halogen-free version Z1G-YMz1KaS mbhz 0.6/1 kV.

Electrical details:
Nominal voltage: 600/1000 Volt
Tested voltage: 3500 Volt

Core colours:
2 cores: Brown, blue
3 cores: Black, brown, grey
4 cores: Black, blue, brown, grey
5 cores: Black, blue, brown, black, grey

Supplied:
All sizes: On reels


 

print

Number of cores and nominal conductor diameter*
(n x mm²) 
Nominal outside diameter
(mm)
Minimum bending radius
(mm)
Permissible current**
(A)
Maximum tensile strength
(N)
Approximate weight
(kg/km)
2 x 10 20.2 141 73 3260 840 
2 x 16 22.2 155 95 3940 1060 
2 x 25 26 182 121 5410 1450 
2 x 35 27 189 146 5830 1710 
2 x 50 30 210 173 7200 2150 
2 x 70 34 238 213 9250 2820 
3 x 10 21 147 61 3530 950 
3 x 16 23.2 162 79 4310 1210 
3 x 25 27 189 101 5830 1680 
3 x 35 SV 25 175 122 5000 1690 
3 x 50 SV 26.9 188 144 5790 2130 
3 x 70 SV 31.4 220 178 7890 2870
3 x 95 SV 35.2 246 211 9910 3770 
3 x 120 SV 39 273 240 10000 4670
3 x 150 SV 42.5 298 271 10000 5630 
3 x 185 SV 46.6 326 304 10000 6860 
3 x 240 SV 54 378 351 10000 9360
3 x 300 SV 57.8 405 396 10000 11380 
4 x 10 22.1 155 61 3910 1070 
4 x 16 24.9 174 79 4960 1470
4 x 25 29.5 207 101 6960 2030 
4 x 35 SV 28.2 197 122 6360 2090 
4 x 50 SV 30.9 216 144 7640 2690 
4 x 70 SV 35.6 249 178 10000 3680 
4 x 95 SV 39.6 277 211 10000 4850 
4 x 120 SV 43.2 302 240 10000 5980 
4 x 150 SV 47.6 333 271 10000 7240 
4 x 185 SV 54.1 379 304 10000 9490 
4 x 240 SV 60.3 422 351 10000 12030 
5 x 10 24.1 169 61 4650 1270
5 x 16 26.9 188 79 5790 1680 

*) SV = sector-shaped.
**) The permissible current applies to 1 cable laid directly underground (basic installation method D of NEN 1010 fifth edition), at a ground temperature of 20 C° and a heat resistance coefficient of the ground of 2.5 K.m/W.

Bos elektro bv ©  |  Oscar Romerolaan 12 , 1216 TK, Hilversum  |  E-mail  |  Telefoon +31 (0)35 623 6000  |  Fax +31 (0)35 623 5968  |  Disclaimer  |  Privacy