Master meter boxes

Meter distribution boxes

Master meter boxes

print

[technical schedule]

MASTER 63 M 3 2A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Cable entry via plastic jacket tube. Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 63A.
Power: 1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding pipe. Clamps for this are supplied with it.
Article number 6063N0003K
Article number 6063N0002K, same, but with shed group 20A.
Article number 6063N0017K, same, but 3 x 5p. 32A.
Article number 6063N0019K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 63 M 4 3A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Cable entry via plastic jacket tube. Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 63A.
Power: 1 built-in socket 5p. 63A. protected by 1 circuit breaker of 40A. and 1 earth leakage switch 63A. 0.3A.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding pipe. Clamps for this are supplied with it.
Article number 6063N0007K
Article number 6063N0008K, same, but with underground cable group 20A.
Article number 6063N0016K, same, but 3 x 5p. 32A.
Article number 6063N0020K, same, but 3 x 5p. 32A. with underground cable group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 63 M 5 4A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Cable entry via plastic jacket tube. Lockable by way of standard cylinder lock
or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 63A.
Power: 2 built-in sockets 5p. 63A. protected by 1 circuit breaker of 40A. and 1
earth leakage switch 63A. 0.3A. per socket.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6063N0011K
Article number 6063N0010K, same, but with shed group 20A.
Article number 6063N0009K, same, but 3 x 5p. 32A.
Article number 6063N0021K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 80 M 3 2A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Suitable for direct metering up to 80A. Cable entry via plastic jacket tube.
Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 80A.
Power: 1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are pre-protected by 1 circuit breaker 50A. and are
protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6080N0003K
Article number 6080N0002K, same, but with shed group 20A.
Article number 6080N0005K, same, but 3 x 5p. 32A.
Article number 6080N0004K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 80 M 4 3A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Suitable for direct metering up to 80A. Cable entry via plastic jacket tube.
Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 80A.
Power: 1 built-in socket 5p. 63A. protected by 1 circuit breaker of 40A. and by 1
earth leakage switch 63A. 0.3A.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are pre-protected by 1 circuit breaker 50A. and are
protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6080N0007K
Article number 6080N0006K, same, but with shed group 20A.
Article number 6080N0008K, same, but 3 x 5p. 32A.
Article number 6080N0005K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 80 M 5 4A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Suitable for direct metering up to 80A. Cable entry via plastic jacket tube.
Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 80A.
Power: 2 built-in sockets 5p. 63A. protected by 1 circuit breaker of 40A. and 1
earth leakage switch 63A. 0.3A. per socket.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are pre-protected by 1 circuit breaker of 50A. and by
1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6080N0011K
Article number 6080N0010K, same, but with shed group 20A.
Article number 6080N0012K, same, but 3 x 5p. 32A.
Article number 6080N0014K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 125 M 4 3A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Suitable for direct metering up to 125A. Cable entry via plastic jacket tube.
Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 125A.
Power: 1 built-in socket 5p. 63A. protected by 1 circuit breaker of 50A. and by
1 earth leakage switch 63A. 0.3A.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are pre-protected by 1 circuit breaker 50A. and are
protected by 1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6125N0003K
Article number 6125N0004K, same, but with shed group 20A.
Article number 6125N0005K, same, but 3 x 5p. 32A.
Article number 6125N0006K, same, but 3 x 5p. 32A. with shed group 20A.
Extra Options MH DIN00 K, fuse gear.

print

[technical schedule]

MASTER 125 M 5 4A KEMA KEUR

IP 44   

Meter unit made of impact-resistant plastic, consisting of:

Meter area: Suitable for direct metering up to 125A. Cable entry via plastic jacket tube.
Lockable by way of standard cylinder lock or padlock.
Distribution area: Lockable with clamp locks.
Main switch: 4p. 125A.
Power: 2 built-in sockets 5p. 63A. protected by 1 circuit breaker of 50A. and 1
earth leakage switch 63A. 0.3A. per socket.
1 built-in socket 5p. 32A. protected by 1 circuit breaker of 32A.
2 built-in sockets 4p. 32A. protected by 1 circuit breaker of 32A. per socket.
The 32A. power groups are pre-protected by 1 circuit breaker of 50A. and by
1 earth leakage switch 63A. 0.03A.
Light: 6 built-in sockets 2p. + earthing 16A. protected by 1 circuit breaker of 16A. per 2 sockets.
The 16A. groups are protected leakage by 1 earth leakage switch 25A. 0.03A.
Stand: Steel pipe frame, heavily galvanized, if necessary anchored by scaffolding
pipe. Clamps for this are supplied with it.
Article number 6125N0007K
Article number 6125N0008K, same, but with shed group 20A.
Article number 6125N0009K, same, but 3 x 5p. 32A.
Article number 6125N0010K, same, but 3 x 5p. 32A. with shed group 20A
Extra Options MH DIN00 K, fuse gear.

Bos elektro bv ©  |  Oscar Romerolaan 12 , 1216 TK, Hilversum  |  E-mail  |  Telefoon +31 (0)35 623 6000  |  Fax +31 (0)35 623 5968  |  Disclaimer  |  Privacy